You want lower energy bills, steady comfort and a plan that proves results across your buildings.
Build your energy baseline
You cannot improve what you don’t measure. Start with an industrial energy audit that maps how your site actually uses power across HVAC, process loads, lighting and plug loads. Pull 12 months of utility data, then trend key meters and sub-meters for at least two weeks to spot schedules, peaks and waste. Pair the numbers with a boots-on-the-ground walkthrough. Check air handlers, chillers, boilers, distribution pumps and terminal units. Verify setpoints, damper positions, valve stroke, filter condition and sensor calibration. Capture photos, thermal images and nameplate data so findings are clear and repeatable.
Translate observations into a prioritized list. Rank fixes by savings, cost and difficulty. Low-cost actions often pay first: correct time schedules, right-size outside air, tighten economizer limits, end simultaneous heating and cooling, fix compressed-air leaks, seal envelope gaps, tune controls. Define energy performance indicators that fit your operation, like kWh per square meter, kWh per ton of cooling or kWh per unit produced. Baseline them now, not later.
Once, I found two stuck economizers during a midnight walkthrough; fixing schedules cut weekday peaks 14 percent with no new equipment.
Document everything inside a short action plan. Include scope, expected savings, rough costs and owners for each task. Set milestones and a measurement and verification approach so you can prove outcomes. If you need outside help, a green building consultancy can speed the audit, model savings, align improvements with certification goals and surface incentives. When the baseline is clear, you know where HVAC energy optimization will move the needle fastest.
Improve HVAC for savings
With your baseline set, focus on control strategies that trim load without hurting comfort. Reset supply air temperature based on outside conditions to reduce chiller lift and reheat. Add static pressure reset so fans slow down when zones need less air. Calibrate thermostats, widen deadbands slightly and enforce occupied, setup and setback modes so equipment rests when spaces do. Sequence chillers by efficiency curves, not size. Reset condenser water temperature as weather allows to improve chiller performance. Fit variable-speed drives on supply and return fans, cooling tower fans and primary or secondary pumps where turndown is valuable.
Tackle ventilation next. Demand-controlled ventilation uses CO₂ or occupancy signals to match outside air to real needs. Economizers should bring in free cooling only when it is truly helpful, with dry-bulb or enthalpy limits set correctly. Review heat recovery effectiveness and bypass logic for shoulder seasons. Fix the basics too: dirty coils, clogged filters and failed actuators waste energy daily. Commission your sensors too; drifting CO₂ or humidity readings can push ventilation and reheat the wrong way.
What could you cut without hurting comfort?
Overlay analytics to flag simultaneous heating and cooling, short cycling or zones that never meet setpoint. Use fault detection to turn noisy data into clear tickets your team can close. For plants with process heat or chilled water, tie process schedules to building loads so systems do not fight each other. Tune hot water and chilled water differential pressure setpoints, then stage pumps by VFD speed instead of bypass. Balance air and water flows after control changes so valves and dampers regain authority. Update equipment schedules using occupancy from access control or WiFi trends. Where it fits, add thermal storage rules so overnight charging shifts load to off-peak hours. A short retuning session after each change confirms comfort and shows savings. These steps give fast, bankable gains that set up deeper retrofits later.
Sustain results with energy management
Quick wins fade without structure. An energy management system gives you the backbone to sustain gains and scale them sitewide. Start simple: connect your building automation system, meters and key equipment to one dashboard that shows real-time demand, consumption and comfort. Set alerts for drift from targets so issues are caught early. Standardize graphics and naming so technicians find the right point fast. Use weekly reviews to close open faults, compare sites and share fixes that worked.
Layer in measurement and verification so savings are provable. Pick a method that fits the project and stick to it so finance, operations and leadership trust the numbers. Publish a scorecard with the energy performance indicators you chose during the audit. Celebrate wins and reset targets each quarter.
Training matters. Teach operators how control sequences work, how resets save energy and how to balance comfort with cost. Short playbooks help new team members keep consistency. A green building consultancy can guide certification paths, align improvements with ESG goals and package projects for incentives or green lending. When deeper retrofits make sense, model lifecycle cost, not just capex. Bundle LED upgrades, VFDs, heat recovery and envelope sealing with chiller or boiler replacements so cash-positive savings fund the plan. Close the loop by storing trends, work orders and as-built sequences inside the system. That is how building energy efficiency becomes durable, not temporary.
Bottom line: Start with a clear audit, improve HVAC controls, then sustain gains with an energy management system.